CONVENTIONAL ZONE MODULE

产品型号:FW841

返回产品
600x600
产品介绍

功能特点

The FW841 conventional zone module is intended to allow Maple Armor intelligent fire alarm control panels to interface and monitor 2-wire conventional detectors in retrofit applications.

The initiating zone can support a mix of 2-wire conventional automatic detectors as well as normally open dry contact alarm initiating devices such as mechanical heat detectors and manual stations.

The Initiating Zone power can be derived either from the SLC loop or be provided by an external UL/ULC listed 24VDC power supply.

SPECIFICATION


SLC Nominal Voltage

24VDC

SLC Voltage Range

15 to 28VDC

SLC Standby Current

10mA

SLC Active Current

31mA

External Nominal Input Power Voltage

24VDC

External Input Power Voltage Range

16 to 28VDC

Max. Line Impedance Output

50 Ω

Max. Impedance for Grounding

6.6 KΩ

Compatible EOLR

2k to 50K Ω

Operating Temperature

32°F to 120°F (0°C to 49°C)

Operating Humidity

0% to 93% RH

Mounting

FW800 base

Dimension

120 mm (L) x 120 mm (W) x 45 mm (H)

Weight (with backbox)

8.7 oz (247 g)

Wiring Gauge

12 to 18 AWG


INSTALLATION


1.?Mount the FW800 base onto a 2X4 or 4x4 electrical box using the screws provided, as illustrated in Figure 1.



Figure 1 Installation Diagram


2. Connect the wires, see Figure 2. There is polarity sensitive between terminal 1 and terminal 2. All circuits are power-limited.



Figure 2 Wiring Diagram (SLC/DCL)


3.?Wire the SLC/DCL to the module, as illustrated in Figure 3.



?(a) Class A or DCLA Circuit



(b) Class B or DCLB Circuit


Figure 3 SLC/DCL Wiring Diagram


4. Connect the input line circuit wires. See Figure 4. The maximum line impedance for input circuit is 50Ω.

??



(a) Class A Circuit



(b) Class B Circuit


Figure 4 Wiring Diagram (Input Line Circuit)


5. Combine the assembled unit to the base using the screws provided.

6.?Apply power to the control unit.


TESTING


1. Before testing, inform the proper authorities that the system is undergoing maintenance and will temporarily be put out of service. Disable the system to prevent unwanted alarms.

2.?Make sure the indicator LED on the detector’s surface is flashing (once every 3 seconds when powered by external 24VDC, or twice every 3 seconds when powered by SLC loop). Flashing 3 times every 3 seconds indicates the module is in trouble condition (for example missing EOLR). Failure to flash indicates a non-functioning module or a faulty wiring. Check the wiring and remount the module.

3. Trigger the input switch to activate a fire signal. The LED should turn to red steady on. Check the event occurrence displayed on LCD of the controller and verify.

4. Once the testing is completed, set the system back to normal operation and inform proper authorities.


MAINTENANCE


Return the module for repair if it fails to flash or alarm during testing. Do not disassemble the module without permission.